Fail-Safe Modules   
7.2 PM-E F pm DC24V PROFIsafe Power Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
76  Installation and Operating Manual, 08/2008, A5E00103686-07 
Diagnostic functions    
The table below provides an overview of the diagnostic functions of the PM-E F pm DC24V 
PROFIsafe. The diagnostic functions are assigned either to one channel or to the entire 
module. 
Table 7- 4  Diagnostic functions of the PM-E F pm DC24V PROFIsafe 
Diagnostic Function*  Fault 
Number 
LED  Effective Range of 
Diagnostics 
Can be 
Assigned 
Parameter
s 
Short circuit    1
H
  SF  Channel  No 
Overload  4
H
  SF  Channel  No 
Overtemperature    5
H
  SF  Module  No 
Wire break    6
H
  SF  Channel  Yes 
Internal error    9
H
  SF  Module  No 
Parameter assignment error    10
H
  SF  Module  No 
Sensor voltage or load voltage missing    11
H
  SF  Module  No 
Communication error    13
H
  SF  Module  No 
Safety-related shutdown    19
H
  SF  Channel  No 
*: Specially for F-modules; display in 
STEP 7
, see "Channel-Specific Diagnostics, Fault Types of Fail-
Safe Modules" table 
 
 
WARNING 
 
Before acknowledging the short-circuit diagnosis, remedy the respective error and validate 
your safety function. To do this, proceed as described in chapter "
Fault Diagnostics 
(Page 
43)".