Fail-Safe Modules 
  7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module 
ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
129 
Special Features of Fault Detection (Application 3.1 and 3.2)  
The following table presents fault detection according to the sensor supply and the 
parameter assignment for the short-circuit test: 
Table 7- 23  EM 4/8 F-DI DC24V PROFIsafe: Fault Detection (Application 3.1 and 3.2) 
Fault detection with internal sensor power supply and 
activated short-circuit test for... 
Example of fault 
Sensor 2-channel equivalent  Sensor 2-channel non-
equivalent 
Short circuit in DI 0 with DI 1  Yes* Yes* 
Short circuit in DI 0 with DI 4  Yes* Yes 
Short circuit in DI 0 with DI 5  Yes* Yes* 
P-short circuit in DI 0  Yes  Yes 
M-short circuit in DI 0  Yes* Yes* 
Discrepancy error  Yes  Yes 
P-short circuit in sensor supply 1  Yes  Yes 
M-short circuit in sensor supply 1, or 
sensor supply 2 defective 
Yes  Yes 
Short circuit in sensor supply 1 with 
sensor supply 2 
Yes  Yes 
Fault in read/test circuit  Yes  Yes 
Supply voltage fault  Yes  Yes 
*: Fault is detected only in case of signal corruption. In other words, the signal read differs from the 
sensor signal (discrepancy error). If there is no signal corruption with respect to the sensor signal, 
fault detection is not possible and is not required from a safety standpoint. 
Requirements for Machine Protection Applications with Category 4 
The following requirements apply for applications in machine protection with category 4: 
●  The wiring between sensors and automation system and between automation system 
and actuators must be designed to state-of-the-art engineering and standards to prevent 
short circuits 
●  All short circuits listed in the above table are covered. It is sufficient to locate a short 
circuit, because two faults are required for it to occur (both signal lines in short circuit 
have an insulation fault). A multiple short circuit analysis is not required. 
Procedures for locating all short circuits are also permissible if single short circuits are not 
located, 
●  provided these do not cause corruption of read signals compared to the sensor signals or 
●  provided they cause corruption of read signals compared to sensor signals in the 
direction that ensures safety.