Fail-Safe Modules   
7.7 4 F-DO DC24V/2A PROFIsafe digital electronic module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
170  Installation and Operating Manual, 08/2008, A5E00103686-07 
 
Note 
The EM 4 F-DO DC24V/2A PROFIsafe carries out a bit pattern test every 15 minutes or so. 
The module then sends an impulse for max. 4 ms. This test is run with a time offset between 
the P and M-switches in order to prevent the actuator from being activated. This impulse 
may cause the corresponding relay to tighten, which may reduce its service life. 
We therefore recommend adhering to the wiring scheme detailed below.  
 
Application 3: Wiring two loads in parallel to each digital output 
Avoiding/Managing Cross Circuits: 
To protect against cross-circuits between P and M-switches in fail-safe digital outputs, we 
recommend the following wiring scheme. This configuration achieves safety class 
SIL3/Category 4/PLe. 
30(
/ 0
'2
0
'2
3
'2
0
'2
3
'2
0
'2
3
'2
0
'2
3
)'2 
/0
.
.
.
.
0
0
.
.
.
.
 
Figure 7-53  Wiring diagram for in each case 2 relays parallel on 1 F-DO of the EM 4 F-
DO DC24V/2A PROFIsafe 
 
 
Note 
With a parallel connection of two relays on one digital output (as shown above) the "wire 
break" fault is only detected if the wire break disconnects both relays from P or M. This 
diagnosis is not safety-related.