Fail-Safe Modules   
7.8 1 F-RO DC24V/AC24..230V/5A Digital Electronic Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
180  Installation and Operating Manual, 08/2008, A5E00103686-07 
Terminal  Designation 
9  OUT 1 
10  OUT 1 
NO contact, channel 0 for fail-safe switching of load 1 
11  OUT 2 
12  OUT 2 
NO contact, channel 1 for fail-safe switching of load 2 
A12  AUX 1  At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3 
to A16 for any PE connection. 
Individual grouping of load current supplies is supported. 
A11  AUX 1  At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3 
to A16 for any PE connection. 
Individual grouping of load current supplies is supported. 
13  OUT 1 
14  OUT 1 
NO contact, channel 0 for fail-safe switching of load 1 
15  OUT 2 
16  OUT 2 
NO contact, channel 1 for fail-safe switching of load 2 
A16  AUX 1  At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3 
to A16 for any PE connection. 
Individual grouping of load current supplies is supported. 
A15  AUX 1  At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3 
to A16 for any PE connection. 
Individual grouping of load current supplies is supported. 
 
 
CAUTION 
 
Wire these terminals in parallel if high currents are generated at OUT 1 or OUT 2 (≥ 50% of 
the rated current of the respective output channel): 
•  For OUT 1: Terminals 9/10 and 13/14 
•  For OUT 2: Terminals 11/12 and 15/16 
Otherwise, high current loads may cause the terminals to heat up.