Diagnostic Data of Fail-Safe Modules   
A.2 Structure and Content of Diagnostic Data 
  ET 200S Distributed I/O System - Fail-Safe Modules 
190  Installation and Operating Manual, 08/2008, A5E00103686-07 
Data Records 0 and 1 of the System Data 
The diagnostic data of a module can be up to 40 bytes long and is located in data records 0 
and 1 of the system data area: 
●  Data record 0 contains 4 bytes of diagnostic data that describe the state of the F-module. 
●  Data record 1 contains 
–  The 4 bytes of diagnostic data of the F-module that are also in data record 0 and 
–  Up to 36 bytes of channel-specific diagnostics data, depending on the F-module (see 
"
Channel-Specific Diagnostics from Byte 8"
). 
Description 
The next section describes the content and structure of the individual diagnostic data bytes.  
General rule: If a fault occurs, the corresponding bit is set to "1". 
Bytes 0 and 1 
The figure below shows the contents of bytes 0 and 1 in the diagnostic data. 
0RGXOHHUURU
)PRGXOHRN
)PRGXOHIDXOWHGWKHQ
%LWVDQGDUHDOVRVHW
([WHUQDOHUURU
&KDQQHOHUURU
0RGXOHFODVV
%
IRU)PRGXOHV
&KDQQHOLQIRUPDWLRQH[LVWV
%\WH
%\WH
 
Figure A-1  Bytes 0 and 1 of Diagnostic Data