SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
257
-25 ... 70 °C for natural convec-
tion (self convection)
-25 ... 60 °C for natural convec-
tion (self convection)
15 A (derating) at 60° ... 70° C
-25 ... 60 °C for natural convec-
tion (self convection)
30 A (derating) at 60° ... 70° C
• EN 60068-2-1 Cold
• EN 60068-2-2 Dry heat
• EN 60068-2-78 Humid heat, constant
• EN 60068-2-14 Temperature change
Remark: The service life of the UPS1100 battery modules (decrease to 50 % of the original capaci-
ty) depends on the battery temperature, at approximately 20 °C: 4 years, 30 °C: 2 years, 40 °C: 1
temperature
Tests (packed for shipping) according to:
• EN 60068-2-1 Cold
• EN 60068-2-2 Dry heat
EN 60068-2-30 Humid heat, cyclic
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
stress in operation
• EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 9 Hz
1 g acceleration in the range 9 - 150 Hz
• EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
• EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
• 1080 - 795 hPa (-1000 - 2000 m)
• For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5 % / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 6-20 Altitude derating (Page 209)
Storage:
1080 - 660 hPa (-1000 - 3500 m)