Cycle and reaction times
5.5 Interrupt response time
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
5-23
Process interrupt processing
Process interrupt processing begins after process interrupt OB40 is called. Higher-priority
interrupts stop process interrupt processing. Direct I/O access is executed during runtime of
the instruction. After process interrupt processing has terminated, cyclic program execution
continues or further interrupt OBs of equal or lower priority are called and processed.
See also
Overview (Page 5-1)
5.5.2 Reproducibility of delay interrupts and watchdog interrupts
Definition of "Reproducibility"
Delay interrupt:
The period that expires between the call of the first instruction in the interrupt OB and the
programmed time of interrupt.
Watchdog interrupt:
The fluctuation width of the interval between two successive calls, measured between the
respective initial instructions of the interrupt OBs.
Reproducibility
The following times apply for the CPUs described in this manual:
Delay interrupt: +/- 200 μs
Watchdog interrupt: +/- 200 μs
These times only apply if the interrupt can actually be executed at this time and if not
interrupted, for example, by higher-priority interrupts or queued interrupts of equal priority.

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals