Memory concept
4.2 Memory functions
CPU 31xC and CPU 31x, Technical data
4-14 Manual, Edition 08/2004, A5E00105475-05
Restart (warm start)
All retentive DBs retain their actual value (non-retentive DBs are also supported by CPUs
with Firmware >= V2.1.0. Non-retentive DBs receive their initial values).
The values of all retentive M, C, T are retained.
All non-retentive user data are initialized:
M, C, T, I, O with "0"
All run levels are initialized.
The process images are deleted.
Reference
Also refer to
CPU memory reset by means mode selector switch
in the section
Commissioning
in the
CPU 31xC and CPU 31x Operating Instructions
.