Analog input module error types
Table 6-14 Analog input module error types
Analog input modules
Error type Meaning Remedy
2AI U
High
Speed
2AI U
Standard
2AI U High
Feature
2AII2WIRE
Standard
4AII2WIRE
ST
2AII2WIRE
High Speed
2AII4WIRE
Standard
2AII2/4WIRE
High Feature
2AI TC
Standard
2AI TC
High
Feature
16
D
10000:
Parameter
assignment
error
Module cannot use the
parameter for the
channel:
Inserted module does
not match the one
configured.
Parameter assignment
error.
Correct the
configuration
(compare actual
and desired
configuration).
Correct the
parameter
assignment
(parameter
assignment of
wire break
diagnosis only
with the
permitted
measuring
ranges).
High Speed
2AI RTD
Standard
2AI RTD High
9
D
01001: Error Internal module error
has occurred
(diagnostic message
on channel 0 applies
to the whole module).
Replace the
module.
ea
ure
7
D
00111: Violation
of hi limit
Value is above the
overrange.
Correct the
module/actuator
match.
8
D
01000:
Violation of lo
limit
Value is below the
underrange.
Correct the
module/actuator
match.
-- -- -- 6
D
00110:
Open circuit
1)
Line to the sensor
interrupted.
Correct the
process wiring.
-- -- -- -- -- -- 21
D
10101:
Reference
channel error
2)
Error on the reference
channel
Check the
reference
module (2AI
RTD Standard).
1) In the case of the 2AI RTD High Feature, a wire break is reported for the measuring and constant-current
lines of the sensor.
2) The following applies for the 2AI TC Standard and 2AI TC High Feature modules:
during configuration with the device database file reference c hannel errors are not reported if the reference