2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
Manual, 04/2007, A5E01076015-01
11
Parameters
2
2.1 Parameters
Table 2-1 Parameters for analog input module
2AI U HS Range of values Default setting Applicability
Group diagnosis (parameter
assignment error, internal error)
• Disable
• Enable
Disable Module
Diagnostics: Overflow/underflow
• Disable
• Enable
Disable Module
Smoothing
• None
• Weak
• Medium
• Strong
None Channel
Enable hardware interrupt
• Disable
• Enable
Disable Module
Type/range of measurement
• De-activated
• ± 2,5 V
• ± 5 V
• ± 10 V
• 1 mA to 5 V
± 10 V Channel
High limit
• low to high limit of the
overrange
27648 Channel
Low limit
• low to high limit of the
overrange
0 Channel
Note
If you deactivate a HS module channel, you do not gain any advantages in terms of speed,
due to the measuring procedure used.