5.2 Wiring unused channels of the analog input modules
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
22 Manual, 04/2007, A5E01076015-01
5.2 Wiring unused channels of the analog input modules
Rules
Pay attention to the following instructions when wiring unused channels:
"Disable" unused input channels when setting parameters.
A disabled channel always returns the value 7FFF
H
.
The cycle time of the 2AI U HS module is always 250 ms.
To adhere to the permissible potential differences (U
CM
), you must wire jumpers on the
terminal module for the unused channels.
TM connection terminal
Channel 0 Channel 1
Analog input module
1 2 3 4 5 6 7 8
2AI U HS
5.3 Using the shield connection
Rules
To prevent interference we recommend the following with the analog electronic modules:
Use shielded wires to the sensors and actuators.
Lay out the wire shields on the shield connection.
Connect the shield connection with low impedance to the ground bus.