Analog value representation
4.4 Effect on analog value representation
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
Manual, 04/2007, A5E01076015-01
17
Voltage measuring ranges: 1 mA to 5 V
Table 4-4 SIMATIC S7 format: Measuring range 1 V to 5 V
Units
Measuring range
1 V to 5 V
Decimal Hexadecimal
Range
> 5,704 32767 7FFF
H
Overflow
5,704
:
5,000145
32511
:
27649
7EFF
H
:
6C01
H
Overrange
5,000
4,000
:
1,000
27648
20736
:
0
6C00
H
5100
H
:
0
H
Rated range
0,999855
:
0,296
-1
:
-4864
FFFF
H
:
ED00
H
Undershoot range
< 0,296 -32768 8000
H
Underflow
4.4 Effect on analog value representation
4.4.1 Effect of the supply voltage and the operating state on analog input values
The input values of the analog modules are dependent on the supply voltage for
electronics/encoders and on the operating state of the PLC (CPU of the DP master). The
table below shows this dependency..
Table 4-5 Dependence of the analog input values on the operating state of the PLC (CPU of the
DP master) and the supply voltage L+
Operating state of the PLC
(CPU of the DP master)
Power supply L+ on
ET 200S (power
module)
Input value of the electronics module with
analog inputs (evaluation possible on the
CPU of the DP master)
Process values L+ present
7FFF
H
until first conversion after startup, or
after assignment of parameters for the
module is completed.
POWER ON RUN
L+ missing 7FFF
H
L+ present Process value POWER ON STOP
L+ missing 7FFF
H
L+ present - POWER OFF -
L+ missing -

Related product manuals