Diagnostics
3.2 Error types
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
14 Manual, 04/2007, A5E01076015-01
3.2 Error types
Analog input module error types
Table 3-1 Error types
Analog input modules Fault type Meaning Remedy
16
D
10000:
Configuration error
Module cannot use the
parameter for the channel:
Inserted module does not
match the one configured.
Faulty parameter assignment.
Correct the configuration
(align actual and preset
configuration).
Correct the parameter
assignment (diagnostics wire
break only for the allowed
measuring range
parameterized).
9
D
01001: Errors Internal module error
(diagnostics message at
channel 0 applies to the entire
module)
Replace the module.
7
D
00111: Violation of
higher limit
Value is above the overrange. Correct the module/actuator
tuning.
2AI U HS
8
D
01000: Lower
value limit fallen
below
Value is below the
underrange.
Correct the module/actuator
tuning.
3.3 Interrupts
Hardware interrupt of analog input modules
%\WHV[DQG[DOZD\V
+
8SSHUOLPLWH[FHHGHG&KDQQHO
8SSHUOLPLWH[FHHGHG&KDQQHO
/RZHUOLPLWYDOXHXQGHUVKRW&KDQQHO
/RZHUOLPLWYDOXHXQGHUVKRW&KDQQHO
%\WH[
%\WH[
Figure 3-1 Structure as of Byte x+4 and Byte x+5 for hardware interrupt (analog input)