EasyManua.ls Logo

Siemens 6ES7134-4FB51-0AB0 - 5 Connecting; Connecting Measuring Sensors

Siemens 6ES7134-4FB51-0AB0
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
Manual, 04/2007, A5E01076015-01
19
Connecting
5
5.1 Connecting measuring sensors
Introduction
You can connect encoders with voltage signals to the 2AI U HS analog input module.
In this chapter you will find out how to connect the measuring sensors and what to watch for
when doing so.
Lines for analog signals
You should use shielded and twisted-pair lines for the analog signals. This reduces the effect
of interference. You should ground the shield of the analog lines at both ends of the line. If
there are differences in potential between the ends of the line, a compensating current flows
via the shield that can interfere with the analog signals. If this is the case, you should only
ground the shield at one end of the line.
Analog input modules
In the case of the analog input modules there is electrical isolation:
Between logic and backplane bus
Between load voltage and the channels The following are used:
Isolation: No link between M
ANA
and the central grounding point (U
ISO
)
Note
Ensure that this potential difference U
ISO
does not exceed the permitted value. If there
is a possibility of exceeding the permitted value, make a connection between terminal
M
ANA
and the central grounding point.
Connection of measuring sensors to analog inputs
Between the measuring lines M- of the input channels and the reference point of the
measuring circuit M
ANA
there can be only a limited potential difference U
CM
(common-mode
voltage). To ensure that the permitted value is not exceeded, you must take different steps
depending on the whether the sensors are isolated or non-isolated. The steps you have to
take are described in this chapter.

Related product manuals