EasyManua.ls Logo

Siemens 6ES7134-4FB51-0AB0 - Page 10

Siemens 6ES7134-4FB51-0AB0
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Properties
1.1 2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
10 Manual, 04/2007, A5E01076015-01
Suppression of interference, limits of error
Common mode interference (U
cm
) < 100 VSS)
> 70 dB
Crosstalk between the inputs > 50 dB
Operational limit
(in the entire temperature range, with reference to
the input range)
± 0,3 %
Basic error limit (operational limit at 25°C with
reference to input range)
± 0,2 %
Temperature error (with reference to the input
range)
±0,01 %/K
Linearity error (with reference to the input range) ± 0,01 %
Repeatability
(in steady state at 25°C with reference to input
range)
± 0,05 %
Data for selecting a sensor
Input ranges (rated value)/input resistance
Voltage
± 10 V/min. 100 kΩ
± 5 V/min. 100 kΩ
± 2.5 V/min. 100 kΩ
1 V - 5 V/min. 100 kΩ
Maximum input voltage for voltage input
(destruction limit)
50 V continuous, 100 V at max. duration of 1 ms
(sampling ratio 1:20)
Connection of the sensors
For measuring voltage
Supported
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
64 x cycle time
128 x cycle time
512 x cycle time
1
DPV1 only
2
Parameter assignment error
Violation of lower limit value
Violation of upper limit value
Open circuit (only with 1 V to 5 V)
Process interrupt lost

Related product manuals