Technical Data  09.02 
14-4  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
R/R unit  6SE70..-.....-1AA0  38-2EH85 41-0EH85 41-3EK85 41-8EK85  
Rated voltage, rated frequency, rated current 
Rated voltage 
Rectifier connection 
Regenerative connection 
 
DC link voltage 
V  
3AC 380V –15% to 480V +10% 
using an (auto) transformer 
1.2 times the voltage of the rectifier connection 
DC 510V –15% to 650V +10% 
Rated frequency f
n
 
Input 
Output 
Hz  
46 to 64  (automatic frequency matching) 
DC 
Rated current 
(rms value) 
With autotransformer
 
 Regenerating, line 
 side 
 Regenerating, unit 
 side 
 Rectifier operation 
Without autotransformer
 
 Regenerating, unit 
 side 
 Rectifier operation 
A  
 
 
784 
 
654 
 
710 
 
654 
 
710 
 
 
 
980 
 
817 
 
888 
 
817 
 
888 
 
 
 
1276 
 
1064 
 
1156 
 
1064 
 
1156 
 
 
 
1702 
 
1481 
 
1542 
 
1481 
 
1542 
 
 
 
Load class I to EN 60146-1-1 of the DC link current (average value) 
in rectifier operation; currents reduced to 92% in regenerative operation 
Rated current 
(average) 
  DC link connection 
 Rectifier operation 
A  821  1023 1333 1780   
Load class II to EN 60146-1-1 of the DC link current (average value) 
in rectifier operation; currents reduced to 92% in regenerative operation 
Rated current  A  747  931  1213  1620   
Base load duration  s    240       
Excess current  A 1121 1396 1820 2430   
Excess current duration  s    60       
Losses, cooling 
Power dissipation 
− 
Maximum 
kW 3.29 3.70 4.84 6.24   
Cooling air requirement  m
3
/s 0.55  0.55  1.0  1.0  
Sound pressure level, dimensions, weight 
Sound pressure level  50 Hz 
                                    60 Hz 
dB(A) 80 
83 
80 
83 
82 
82 
82 
82 
 
Size 
Width 
Height 
Depth 
 
mm 
mm 
mm 
H 
508 
1400 
551 
H 
508 
1400 
551 
K 
800 
1725 
550 
K 
800 
1725 
550 
 
Weight app.  kg 175  175 450 470   
 
Parallel units (-1AD0) of size K for connecting in parallel have the same technical data as the corresponding 
"basic units" (-1AA0). Please note the unit correspondence and notes of Section 3.7! 
The permissible output current in parallel mode is reduced (due to current division between the power sections) 
by 10 % as compared to the sum of the rated currents of the separate power sections. 