09.02  Technical Data 
Siemens AG    6SE7087 6AK85-1AA0 
14-5 
Rectifier/Regenerating Unit    Operating Instructions 
R/R unit  6SE70..-.....-1AA0  22-7FC85 24-1FC85 27-2FC85 28-8FC85   
Rated voltage, rated frequency, rated current 
Rated voltage 
Rectifier connection 
Regenerative connection 
 
DC link voltage 
V  
3AC 500V –15% to 600V +10% 
using an (auto) transformer 
1.2 times the voltage of the rectifier connection 
DC 675V –15% to 810V +10% 
Rated frequency f
n
 
Input 
Output 
Hz  
46 to 64  (automatic frequency matching) 
DC 
Rated current 
(rms value) 
With autotransformer
 
 Regenerating, line 
 side 
 Regenerating, unit 
 side 
 Rectifier operation 
Without autotransformer
 
 Regenerating, unit 
 side 
 Rectifier operation 
A  
 
 
26 
 
22 
 
24 
 
22 
 
24 
 
 
 
40 
 
33 
 
36 
 
33 
 
36 
 
 
 
69 
 
57 
 
62 
 
57 
 
62 
 
 
 
90 
 
75 
 
82 
 
75 
 
82 
 
 
 
Load class I to EN 60146-1-1 of the DC link current (average value) 
in rectifier operation; currents reduced to 92% in regenerative operation 
Rated current 
(average) 
  DC link connection 
 Rectifier operation 
A 27 41 72 94   
Load class II to EN 60146-1-1 of the DC link current (average value) 
in rectifier operation; currents reduced to 92% in regenerative operation 
Rated current  A 25 37 66 86   
Base load duration  s    240 
Excess current  A 37 56 98 128   
Excess current duration  s    60 
Losses, cooling 
Power dissipation 
− 
Maximum 
kW 0,19 0,21 0,29 0,35   
Cooling air requirement  m
3
/s 0,028 0,028 0,028 0,028   
Sound pressure level, dimensions, weight 
Sound pressure level dB(A) 60 60 60 60   
Size 
Width 
Height 
(without securing bracket) 
Depth 
 
mm 
mm 
 
mm 
C 
180 
600 
 
350 
C 
180 
600 
 
350 
C 
180 
600 
 
350 
C 
180 
600 
 
350 
 
Weight app.  kg 23  23 23 23   
AoteWell Automation Sales Team
Buy Siemens PLC HMI Drives at AoteWell.com