Settings
General Information
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Phase sequence
•
ABC
•
ACB
ABC
Measuring Point I-3ph
Addr. Parameter C Setting Options Default Setting
General
_:8881:115 CT 3-phase:CT connec-
tion
•
not assigned
•
3-phase + IN
•
3-phase
•
3-phase + IN-separate
•
3-phase, 2 primary CT
•
2ph, 2p. CT + IN-sep
3-phase + IN
_:8881:127 CT 3-phase:Tracking
•
inactive
•
active
active
_:8881:130 CT 3-phase:Measuring-
point ID
0 to 100 0
CT phases
_:8881:101 CT 3-phase:Rated
primary current
1.0 A to 100000.0 A 1000.0 A
_:8881:102 CT 3-phase:Rated secon-
dary current
•
1 A
•
5 A
1 A
_:8881:117 CT 3-phase:Current
range
•
1.6 x IR
•
100 x IR
100 x IR
_:8881:118 CT 3-phase:Internal CT
type
•
CT protection
•
CT measurement
•
CT Process bus
CT protection
_:8881:116 CT 3-phase:Neutr.point
in dir.of ref.obj
•
no
•
yes
yes
_:8881:114 CT 3-phase:Inverted
phases
•
none
•
AC
•
BC
•
AB
none
_:8881:107 CT 3-phase:CT error
changeover
1.00 to 10.00 1.00
_:8881:108 CT 3-phase:CT error A 0.5 % to 50.0 % 5.0 %
_:8881:109 CT 3-phase:CT error B 0.5 % to 50.0 % 15.0 %
CT IN
_:8881:104 CT 3-phase:Rated
primary current
1.0 A to 100000.0 A 1000.0 A
_:8881:105 CT 3-phase:Rated secon-
dary current
•
1 A
•
5 A
1 A
_:8881:119 CT 3-phase:Current
range
•
1.6 x IR
•
100 x IR
100 x IR
_:8881:120 CT 3-phase:Internal CT
type
•
CT protection
•
CT measurement
•
CT Process bus
CT protection
5.8
Power-System Data
5.8 Settings
124 SIPROTEC 5, Fault Recorder, Manual