EasyManua.ls Logo

Siemens 7KE85 - Information List

Siemens 7KE85
490 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
_:10021:106 Trigger Ssum 1:Min.
trigger
1 A @ 100 Irated 0.36 VA to 60000.00 VA 138.56 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 692.82 VA
_:10021:114 Trigger Ssum 1:Min.
trigger hysteresis
1.010 p.u. to 1.100 p.u. 1.020 p.u.
_:10021:103 Trigger Ssum 1:dM/dt
rise active
•
no
•
yes
no
_:10021:107 Trigger Ssum 1:dM/dt
rise (/Filter time)
1 A @ 100 Irated 0.36 VA to 60000.00 VA 34.64 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 173.21 VA
_:10021:115 Trigger Ssum 1:dM/dt
rise hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:10021:104 Trigger Ssum 1:dM/dt
drop active
•
no
•
yes
no
_:10021:108 Trigger Ssum 1:dM/dt
drop (/Filter time)
1 A @ 100 Irated 0.36 VA to 60000.00 VA 34.64 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 173.21 VA
_:10021:116 Trigger Ssum 1:dM/dt
drop hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:10021:112 Trigger Ssum 1:Filter
time
2cyclesto250 cycles 2 cycles
Trigger Psw #
_:1 Trigger Psw #:Mode
•
off
•
on
•
test
off
_:100 Trigger Psw #:X reach 1 A 0.100 Ω to 600.000 Ω 100.000 Ω
5 A 0.020 Ω to 120.000 Ω 20.000 Ω
_:101 Trigger Psw #:R (ph-g) 1 A 0.100 Ω to 600.000 Ω 100.000 Ω
5 A 0.020 Ω to 120.000 Ω 20.000 Ω
_:102 Trigger Psw #:R (ph-ph) 1 A 0.100 Ω to 600.000 Ω 200.000 Ω
5 A 0.020 Ω to 120.000 Ω 40.000 Ω
Information List
No.
Information Data Class
(Type)
Type
Trigger Psum 1
_:9901:54 Trigger Psum 1:Inactive SPS O
_:9901:52 Trigger Psum 1:Behavior ENS O
_:9901:53 Trigger Psum 1:Health ENS O
_:9901:301 Trigger Psum 1:Trigger active SPS O
Trigger Qsum 1
_:9961:54 Trigger Qsum 1:Inactive SPS O
_:9961:52 Trigger Qsum 1:Behavior ENS O
_:9961:53 Trigger Qsum 1:Health ENS O
_:9961:301 Trigger Qsum 1:Trigger active SPS O
Trigger Ssum 1
_:10021:54 Trigger Ssum 1:Inactive SPS O
_:10021:52 Trigger Ssum 1:Behavior ENS O
_:10021:53 Trigger Ssum 1:Health ENS O
_:10021:301 Trigger Ssum 1:Trigger active SPS O
7.5.4.10
Fault Recorder
7.5 Trigger Functions 3-Phase
346 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Table of Contents