SMART 7KT0210 Manual
Parameterization with function keys
Sequence Function Range or Selection
Factory
Setting
1 Password 0000to9998 1000
1.1 Changepassword No/Yes No
2 New password 0000to9998 1000
3 Network selection 3P4W/3P3W/1P2W-R/1P2W-Y/1P2W-B 3P4W
4 CTsecondary 1OR5 5
5 CTprimary 5to10000,IfCTSECis5A
1to10000,IfCTSECis1A
5
6 PT secondary 100to500 350
7 PT primary 100to500K 350
8 SlaveID 1to255 1
9 BaudRate 300,600,1200,2400,4800,9600,19200 9600
10 Parity None/EVEN/ODD none
11 StopBit 1 or 2 1
12 Backlightofftime 0000 to 7200 0000
13 DemandIntervalmethod Sliding/Fixed Sliding
14 DemandIntervalduration 1 to 30 min 15min
15 DemandIntervallength 1 to 30 min 1 min
16 ScrollPage Auto/Manual Auto
17 Factory default Yes/No No
18 Reset energy Yes/No No
18.1 Password 0001to9998 1001
18.2 Source Selection Main/DG Main
18.2.1 Reset kWh Yes/No No
18.2.2 ResetkVArh Yes/No No
18.2.3 ResetkVAh Yes/No No
19 ResetONHour Yes/No No