FUN INF Description ASDU COT
1 SE, GI
160 24 Setting G2 selected
20 Ack, Nak
160 27 Binary Input 1 1 SE, GI
160 28 Binary Input 2 1 SE, GI
160 29 Binary Input 3 1 SE, GI
160 30 Binary Input 4 1 SE, GI
160 36 Trip Circuit Fail 1 SE, GI
160 64 Start/Pick-up L1 2 SE, GI
160 65 Start/Pick-up L2 2 SE, GI
160 66 Start/Pick-up L3 2 SE, GI
160 67 Start/Pick-up N 2 SE, GI
160 68 General Trip 2 SE
160 69 Trip L1 2 SE
160 70 Trip L2 2 SE
160 71 Trip L3 2 SE
160 84 General Start/Pick-up 2 SE, GI
160 85 Breaker Failure 2 SE
160 90 Trip I> 2 SE
160 91 Trip I>> 2 SE
160 92 Trip In> 2 SE
160 93 Trip In>> 2 SE
183 10 51-1 2 SE, GI
183 11 50-1 2 SE, GI
183 12 51N-1 2 SE, GI
183 13 50N-1 2 SE, GI
183 14 51G-1 2 SE, GI
183 15 50G-1 2 SE, GI
183 16 51-2 2 SE, GI
183 17 50-2 2 SE, GI
183 18 51N-2 2 SE, GI
183 19 50N-2 2 SE, GI
183 20 51G-2 2 SE, GI
183 21 50G-2 2 SE, GI
183 34 50BF Stage 2 2 SE, GI
183 35 49-Alarm 2 SE, GI
183 36 49-Trip 2 SE, GI
2 SE, GI
183 53 E/F Out
20 Ack, Nak
183 56 50BF Stage 1 2 SE, GI
183 62 37-1 2 SE, GI
183 63 37-2 2 SE, GI
183 100 CB Alarm 1 SE, GI
183 101 Trip Circuit Fail 1 2 SE, GI
183 102 Trip Circuit Fail 2 2 SE, GI
183 103 Trip Circuit Fail 3 2 SE, GI
183 114 Close CB Failed 1 SE, GI
183 115 Open CB Failed 1 SE, GI
183 123 CB Total Trip Count 1 SE, GI
183 124 CB Delta Trip Count 1 SE, GI