Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices Chapter 4 - Page 17 of 70
FUN INF Description ASDU COT
1 SE
183 126 Reset CB Total Trip Count
20 Ack, Nak
1 SE
183 127 Reset CB Delta Trip Count
20 Ack, Nak
183 129 I^2t CB Wear 1 SE, GI
1 SE
183 130 Reset I^2t CB Wear
20 Ack, Nak
183 163 Trip Time Alarm 1 SE
183 164 Close Circuit Fail 1 2 SE, GI
183 165 Close Circuit Fail 2 2 SE, GI
183 166 Close Circuit Fail 3 2 SE, GI
183 167 Close Circuit Fail 2 SE, GI
183 181 CB Total Trip Count 4 SE
183 182 CB Delta Trip Count 4 SE
183 222 37-PhA 2 SE, GI
183 223 37-PhB 2 SE, GI
183 224 37-PhC 2 SE, GI
183 231 50BF-PhA 2 SE, GI
183 232 50BF-PhB 2 SE, GI
183 233 50BF-PhC 2 SE, GI
183 234 50BF-EF 2 SE, GI
183 239 In Fault Current 4 SE
183 240 Ia Fault Current 4 SE
183 241 Ib Fault Current 4 SE
183 242 Ic Fault Current 4 SE
183 243 Ig Fault Current 4 SE
185 43 General Trip 2 SE, GI
185 50 I1 Fault Current 4 SE
185 51 I2 Fault Current 4 SE
185 52 IEq Fault Current 4 SE
185 53 IUn Fault Current 4 SE
185 54 81B 1 SE, GI
185 55 14-1 1 SE, GI
185 56 14-2 1 SE, GI
185 57 14-3 1 SE, GI
185 58 14-4 1 SE, GI
185 59 46 1 SE, GI
185 60 48-1 1 SE, GI
185 61 48-2 1 SE, GI
185 62 Temp-1 Trip 1 SE, GI
185 63 Temp-1 Alarm 1 SE, GI
185 64 Temp-1 Fail 1 SE, GI
185 65 Temp-2 Trip 1 SE, GI
185 66 Temp-2 Alarm 1 SE, GI
185 67 Temp-2 Fail 1 SE, GI
185 68 Temp-3 Trip 1 SE, GI
185 69 Temp-3 Alarm 1 SE, GI
185 70 Temp-3 Fail 1 SE, GI