Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices Chapter 4 - Page 47 of 70
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
900 User SP Command 1 0,2 2 2
901 User SP Command 2 0,2 2 2
902 User SP Command 3 0,2 2 2
903 User SP Command 4 0,2 2 2
904 User SP Command 5 0,2 2 2
905 User SP Command 6 0,2 2 2
906 User SP Command 7 0,2 2 2
907 User SP Command 8 0,2 2 2
910 81B 0,2 2 2
911 14-1 0,2 2 2
912 14-2 0,2 2 2
913 14-3 0,2 2 2
914 14-4 0,2 2 2
915 46 0,2 2 2
916 48-1 0,2 2 2
917 48-2 0,2 2 2
918 Temp-1 Trip 0,2 2 2
919 Temp-1 Alarm 0,2 2 2
920 Temp-1 Fail 0,2 2 2
921 Temp-2 Trip 0,2 2 2
922 Temp-2 Alarm 0,2 2 2
923 Temp-2 Fail 0,2 2 2
924 Temp-3 Trip 0,2 2 2
925 Temp-3 Alarm 0,2 2 2
926 Temp-3 Fail 0,2 2 2
927 Temp-4 Trip 0,2 2 2
928 Temp-4 Alarm 0,2 2 2
929 Temp-4 Fail 0,2 2 2
930 Temp-5 Trip 0,2 2 2
931 Temp-5 Alarm 0,2 2 2
932 Temp-5 Fail 0,2 2 2
933 Temp-6 Trip 0,2 2 2
934 Temp-6 Alarm 0,2 2 2
935 Temp-6 Fail 0,2 2 2
954 50BCL 0,2 2 2
955 50BCL Block 0,2 2 2
956 50BCL CBFail 0,2 2 2
958 No Accel 0,2 2 2
959 Motor Start Counter Alarm 0,2 2 2
960 Total Run Hrs Alarm 0,2 2 2
961 66 Restart Inhibit 0,2 2 2