7SR105 Rho Technical Manual
Chapter 4 - Page 48 of 70 © 2018 Siemens Protection Devices
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
962 Restart Inhibit 0,2 2 2
963 49 Restart Inhibit 0,2 2 2
964 Motor Fail To Run 0,2 2 2
965 66 Starts Exceeded 0,2 2 2
966 Motor Starting 0,2 2 2
967 Motor Running 0,2 2 2
968 Motor Stopped 0,2 2 2
969 49 Load Alarm 0,2 2 2
970 49 Overload Alarm 0,2 2 2
971 46 PH REV 0,2 2 2
972 Close CB Failed 0,2 2 2
973 Open CB Failed 0,2 2 2
5.3.2 Double Bit Input Points
The default double bit input event buffer size is set to allow 100 events.
Double bit inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Double Bit Input Points
Static (Steady-State) Object Number: 3
Change Event Object Number: 4
Static Variation reported when variation 0 requested: 1 (Double Bit Input w/o status)
or 2 (Double Bit Input with status)
Change Event Variation reported when variation 0 requested: 1 (Double Bit Input Change w/o Time)
or 2 (Double Bit Input Change with Absolute Time)
or 3 (Double Bit Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 3
Default Variation
Event Object 4
0 CB 1 0,2 1 3
10 User DP Command 1 0,2 1 3
11 User DP Command 2 0,2 1 3
12 User DP Command 3 0,2 1 3
13 User DP Command 4 0,2 1 3
14 User DP Command 5 0,2 1 3
15 User DP Command 6 0,2 1 3
16 User DP Command 7 0,2 1 3
17 User DP Command 8 0,2 1 3
5.3.3 Binary Output Status Points and Control Relay Output Blocks