EasyManua.ls Logo

Siemens 7SR105 Rho - Page 149

Siemens 7SR105 Rho
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR105 Rho Technical Manual
Chapter 4 - Page 56 of 70 © 2018 Siemens Protection Devices
Analog inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
31 Ia Primary 0,3 2 4 1.000 10.000
32 Ib Primary 0,3 2 4 1.000 10.000
33 Ic Primary 0,3 2 4 1.000 10.000
34 Ia Secondary 0,3 2 4 100.000 0.100
35 Ib Secondary 0,3 2 4 100.000 0.100
36 Ic Secondary 0,3 2 4 100.000 0.100
37 Ia Nominal 0,3 2 4 100.000 0.100
38 Ib Nominal 0,3 2 4 100.000 0.100
39 Ic Nominal 0,3 2 4 100.000 0.100
43 In Primary 0,3 2 4 1.000 10.000
44 In Secondary 0,3 2 4 100.000 0.100
45 In Nominal 0,3 2 4 100.000 0.100
46 Ig Primary 0,3 2 4 1.000 10.000
47 Ig Secondary 0,3 2 4 1000.000 0.100
48 Ig Nominal 0,3 2 4 1000.000 0.100
51 Izps Nominal 0,3 2 4 100.000 0.100
52 Ipps Nominal 0,3 2 4 100.000 0.100
53 Inps Nominal 0,3 2 4 100.000 0.100
95 Active Setting Group 0,3 2 4 1.000 1.000
108 I Phase A Max 0,3 2 4 1.000 10.000
109 I Phase B Max 0,3 2 4 1.000 10.000
110 I Phase C Max 0,3 2 4 1.000 10.000
113 Ig Max 0,3 2 4 1.000 10.000
135 CB Total Trip Count 0,3 1 3 1.000 1.000
136 CB Delta Trip Count 0,3 1 3 1.000 1.000
165 Ia Last Trip 0,3 1 3 1.000 Disabled
166 Ib Last Trip 0,3 1 3 1.000 Disabled
167 Ic Last Trip 0,3 1 3 1.000 Disabled
171 In Last Trip 0,3 1 3 1.000 Disabled
172 Ig Last Trip 0,3 1 3 1.000 Disabled

Table of Contents