Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices Chapter 4 - Page 57 of 70
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
184 CB Wear A 0,3 1 3 0.000 1000000.000
185 CB Wear B 0,3 1 3 0.000 1000000.000
186 CB Wear C 0,3 1 3 0.000 1000000.000
187 CB Wear A Remaining 0,3 1 3 1.000 1.000
188 CB Wear B Remaining 0,3 1 3 1.000 1.000
189 CB Wear C Remaining 0,3 1 3 1.000 1.000
190 CB Wear Minimum 0,3 1 3 1.000 1.000
198 I1 Last Trip 0,3 1 3 1.000 Disabled
199 I2 Last Trip 0,3 1 3 1.000 Disabled
200 IEq Last Trip 0,3 1 3 1.000 Disabled
201 IUn Last Trip 0,3 1 3 1.000 Disabled
203 Thermal Capacity 0,3 2 4 1.000 10.000
204 Thermal Capacity Available 0,3 2 4 1.000 10.000
205 Last Motor Start Tim 0,3 2 4 1.000 1.000
206 Thermal Capacity Last Start 0,3 2 4 1.000 1.000
207 Last Start Max Current 0,3 2 4 1.000 100.000
208 Last Start Min Voltage 0,3 2 4 1.000 10.000
209 Time To Trip 0,3 2 4 1.000 10.000
210 Thermal Time To Star 0,3 2 4 1.000 10.000
211 CurrentMotorRunTimeM 0,3 2 4 1.000 60.000
212 MotorTotalRunTimeMet 0,3 2 4 1.000 60.000
213 AverageMotorRunTimeM 0,3 2 4 1.000 60.000
214 Time Before Run Time 0,3 2 4 1.000 10.000
215 MotorStopTimeMeter 0,3 2 4 1.000 60.000
216 MotorNumStartsMeter Meter 0,3 2 4 1.000 1.000
217 MotorEmStartsMeter Meter 0,3 2 4 1.000 1.000
218 A66NumberOfStartsMet 0,3 2 4 1.000 1.000
219 RestartInhibitTimerM 0,3 2 4 1.000 10.000
220 Temp1 0,3 2 4 1.000 1.000
221 Temp2 0,3 2 4 1.000 1.000
222 Temp3 0,3 2 4 1.000 1.000
223 Temp4 0,3 2 4 1.000 1.000
224 Temp5 0,3 2 4 1.000 1.000

Table of Contents