Plant operation, quick access
5
Operate hot water
55
Siemens Graphical User Interface UI400 CE1U2348en
Building Technologies 2014-06-03
CAUTION
Danger of burns
.
Excessively hot water can result in burns.
Set the nominal set points so th
at scalding at the taps is not possible.
To set the nominal setpoint for hot water, proceed in the manner as described for
the temperature page ("Set comfort setpoint").
Settings:
l The phases are defined in the time switch program during which hot water is
provided.
l Hot water is heated to the nominal setpoint during these phases.
To set the time program for hot water, proceed in the manner as described for the
temperature page.
Modify nominal setpoint
Set the time program