Troubleshooting 3500/42 Operation and Maintenance
194
6.3 System Event List Messages
This section describes the System Event List Messages that are entered by the
Proximitor/Seismic Monitor and gives an example of one.
Example of a System Event List Message:
Sequence
Number
Event
Information
Event
Number
Class Event
Date
DDMMYY
Event
Time
Event
Specific
Slot
0000000123 Device Not
Communicating
32 1 02/01/90 12:24:31:99 5L
Sequence Number: The number of the event in the System Event List (for
example 123).
Event Information: The name of the event (for example Device Not
Communicating).
Event Number: Identifies a specific event.
Class: Used to display the severity of the event. The following
classes are available:
Class Value Classification
0
1
2
3
Severe/Fatal Event
Potential Problem Event
Typical logged Event
Reserved
Event Date: The date the event occurred.
Event Time: The time the event occurred.
Event Specific: It provides additional information for the events that use this
field.
Slot: Identifies the module that the event is associated with. If a
half-height module is installed in the upper slot or a full-
height module is installed, the field will be 0 to 15. If a half-
height module is installed in the lower slot, then the field will
be 0L to 15L. For example, a module installed in the lower
position in slot 5 would be 5L.