3500/42 Operation and Maintenance Troubleshooting
195
The following System Event List Messages may be placed in the list by the
Proximitor/Seismic Monitor and are listed in numerical order. If an event marked with a star
(*) occurs the Proximitor/Seismic Monitor will stop alarming. If you are unable to solve any
problems contact your nearest Bently Nevada Corporation office.
Flash Memory Failure
Event Number: 11
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module as soon as possible.
EEPROM Memory Failure
Event Number: 13
Event Classification: Potential Problem or Severe / Fatal Event
Action: Replace the Monitor Module as soon as possible.
Device Not Communicating
Event Number: 32
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
- the Monitor Module
- the rack backplane
Device Is Communicating
Event Number: 33
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
- the Monitor Module
- the rack backplane
* Neuron Failure
Event Number: 34
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module immediately.
Monitor Module will stop alarming.
* I/O Module Mismatch
Event Number: 62
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected
in the software. If the correct I/O module is installed, there may be a
fault with the Monitor Module or the Monitor I/O module.
Monitor Module will stop alarming.