EasyManua.ls Logo

Siemens Cerberus CS1140 - User Function; Notes for Parameterization Extinguishing (E3 G080) Via Algoworks

Siemens Cerberus CS1140
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
005109_b_en−2
11
Fire & Security Products
Siemens Building Technologies Group
07.2004
5 User function
5.1 Notes for parameterization ’Extinguishing’
(E3G080) via AlgoWorks
Evacuation
Fire detector
activated
Extinguishing
released
Fault
System ON
Automatic
release
blocked
Autom.+Man.
release
blocked
Switch off
warning
panel
Switch off
sounder
Emergency
stop
Cerberus
B3Q440
Á
À
Â
Ã
Loss of extinguishing
agent
Function, Outline description Action on system
AlgoWorks
,p
y
Value Default 1)
Acknowledgement ’Extinguishing released’
Acknowledgement active (confirmation message)
Acknowledgement inactive
autom. acknowledgement
Ļ
j
Ļ
Detection line ’Stop-/Blocking button’
Autom.+ Manual release blocked
Autom. release blocked
no extinguishing release
no extinguishing release
0
1
0
Activation time
Permissible operating time main valve
Value 0...240: > active for 0...240 sec.
Value 255: > active until reset
0..240
255
120
Flooding time
Permissible operating time sector valve
Value 0...240: > active for 0...240 sec.
Value 255: > active until reset
0..240
255
30
Evacuation time
Delay sector valve 0...240 sec.
0..240
16
Evacuation time upon STOP
no restart (Evacuation time is not reset)
new start (Evacuation time is reset)
time continues running
time is restarted
0
1
0
Activation and running mode of alarm horn
Pre-alarm/evacuation/actuated > continuous
Pr-alarm > pulsating/evacuation/actuated > continuous
Pre-alarm > continuous/evacuation/actuated > pulsating
Pre-alarm/evacuation/actuated > pulsating
Evacuation/actuated > continuous
Evacuation/actuated > pulsating
Horn activated according to programming
0
8
16
24
1
17
0
Switch off alarm horn
switch off via AlgoPilot ’CT’ or ’B3Q440’ Â
switch off via ’B3Q440’ Â only
Horn turned off
Horn turned off
0
2
2