7 Overview of operating functions
7.1 Functions ’Extinguishing control −> REVISION’
and ’Extinguishing control −> TEST’
Function Purpose achieved blocked
Extinguishing control
−> REVISION
Permits activation of sequence of functions with-
out horn, illuminated warning panel and valves
(’active’ status visible at maintenance LEDs
E3G080 see following table chapter 7.1.1)
Permits the disconnection of the path ’Extin-
guishing released’ via AlgoPilot, e.g. for the test-
ing of third party extinguishing systems etc.
î via AlgoPilot ’CT11’
î via switch ’S1’ on E3G080
î Valves
î Illuminated warning panel
î Alarm horn
î Path ’Extinguishing relea-
sed’
Extinguishing control
−> TEST
Permits normal sequence, but without activating
the valves
î via AlgoPilot ’CT11’ î Valves
7.1.1 Anzeigen Test-LEDs
LED
State
Active
Short circuit
Open line
H1
Sector valve
H2
Main valve
H3
Alarm horn
continuously on
rapid flashing
slow flashing
H4
Illuminated warning panel
LEDs H1...H4 are always active
7.2 AlgoPilot ’CT11’ list of functions ’SECTION’
Function list SECTION ’extinguishing’
(based on standard text ’english international’)
Notes
BLOCKING autom. extinguishing
î
also possible at operating unit extinguishing 1)
ENABLING autom. extinguishing
î also possible at operating unit extinguishing 1)
BLOCKING autom. & man. exting. release
î also possible at operating unit extinguishing 1)
ENABLING autom. & man. exting. release
a
so
poss
e
a
opera
ng
un
ex
ngu
s
ng
all DETECTOR zones −> OFF
all DETECTOR zones −> ON
all DETECTOR zones −> TEST
î concerns all detectors in the extinguishing SECTION
all DETECTOR zones −> TEST OFF
concerns
a
e
ec
ors
n
e
ex
ngu
s
ng
all DETECTOR zones −> INSTALL. TEST
all DETECTOR zones −> INSTALL. TEST OFF
Extinguishing control −> REVISION
Extinguishing control −> REVISION OFF
î blocks valves, horn, illuminated warning panel,
acknowledgement
Is also possible on E3G080 by means of switch ’S1’
Extinguishing control −> TEST
Extinguishing control −> TEST OFF
î blocks valves
Initiate TEST ’horn’ î briefly activates alarm horn (approx. 5 sec.)
Initiate TEST ’warning panel’ î briefly activates illuminated warning panel
(approx. 5 sec.)
1)
Blocking and enabling also possible ’alternating’
Blocking via AlgoPilot ’CT11’ and enabling via ’B3Q440’ or vice versa