Configuration and operation
4.9 STEP 7 configuration
CP 1242-7 GPRS V2
84 Operating Instructions, 10/2016, C79000-G8976-C311-02
Triggering sending of messages
You configure the triggering of the individual messages (e-mail, SMS message) in the
"Trigger" tab of the message editor with the parameter "E-mail trigger".
One of the following events triggers sending of the message:
CPU changes to STOP.
CPU changes to RUN.
The connection to the partner is interrupted.
The connection to the partner is re-established.
Connection establishment has failed.
TeleService session has started.
TeleService session has ended.
The E-mail trigger "Use PLC tag" is triggered.
For the trigger to send the message, the edge change (0 → 1) of the trigger bit "PLC
variable for trigger" is evaluated. The trigger bit must be set by the user program. A
separate trigger bit can be configured for each message.
If the memory area of the trigger bit is in the bit memory or in a data block, the trigger bit
is reset to zero when the message is sent. In all other cases, you need to reset the trigger
bit with the user program
Weak mobile wireless network (only for sending SMS messages)
Requirements and necessary information
Remember the following requirements in the CP configuration for the transfer of messages:
Enabling telecontrol communication ("Communication types") parameter group
Activating security functions
Additionally for e-mails: Configuring the "E-mail configuration" parameter group
To do this, you require the following information:
Access data of the SMTP server: Address, port number, user name, password
When using STARTTLS or SSL/TLS: Certificate of the e-mail service provider
Email address of the recipient
Include value: Transfer the value of a PLC tag with a message
If you enable the option "Include value" in the "Trigger" parameter group, the CP sends a
value for the placeholder $$ from the memory area of the CPU in the message. To do this
enter "$$" as a placeholder for the value to be sent in the message text.
Select a PLC tag whose value will be integrated in the message. The value is entered in the
message text instead of the placeholder $$.
$$ can be a placeholder for data point types with a simple data type up to a size of 32 bits.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CP 1242-7 GPRS V2 and is the answer not in the manual?

Siemens CP 1242-7 GPRS V2 Specifications

General IconGeneral
BrandSiemens
ModelCP 1242-7 GPRS V2
CategoryController
LanguageEnglish

Related product manuals