Enable identifier for processing status
If this option is enabled in STEP 7, a status is output on the CP that provides information
about the processing status of the sent message. The status is written to a PLC tag of the
type DWORD. Select this tag via the "PLC tag for processing status" box.
The meaning of the statuses is as follows:
Table 4- 4 SMS: Meaning of the status ID output in hexadecimal format
Status
Meaning
0000
Transfer completed free of errors
0001 Error in the transfer, possible causes:
SIM card invalid
No network
Wrong destination phone number (number not reachable)
Table 4- 5 E-mails: Meaning of the status ID output in hexadecimal format
Status
Meaning
0000
Transfer completed free of errors
82xx Other error message from the e-mail server
Apart from the leading "8", the status corresponds to the three-digit error number of the
SMTP protocol.
8401 No channel available
Possible cause: There is already an e-mail connection via the CP. A second connection
cannot be set up at the same time.
8403
No TCP/IP connection could be established to the SMTP server.
8405
The SMTP server has denied the login request.
8406 An internal SSL error or a problem with the structure of the certificate was detected by the
SMTP client.
8407
Request to use SSL was denied.
8408
The client could not obtain a socket for creating a TCP/IP connection to the mail server.
8409 It is not possible to write via the connection. Possible cause: The communications partner
reset the connection or the connection aborted.
8410 It is not possible to read via the connection. Possible cause: The communications partner
terminated the connection or the connection was aborted.
8411
Sending the e-mail failed. Cause: There was not enough memory space for sending.
8412
The configured DNS server could not resolve specified domain name.
8413 Due to an internal error in the DNS subsystem, the domain name could not be resolved.
8414
An empty character string was specified as the domain name.
8415
An internal error occurred in the cURL module. Execution was aborted.
8416
An internal error occurred in the SMTP module. Execution was aborted.
8417 Requests to SMTP on a channel already being used or invalid channel ID. Execution was
aborted.
8418
Sending the e-mail was aborted. Possible cause: Execution time exceeded.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CP 1242-7 GPRS V2 and is the answer not in the manual?

Siemens CP 1242-7 GPRS V2 Specifications

General IconGeneral
BrandSiemens
ModelCP 1242-7 GPRS V2
CategoryController
LanguageEnglish

Related product manuals