Configuration
4.10 Data points
CP 1243-1
100 Operating Instructions, 04/2017, C79000-G8976-C365-03
Event trigger
The value of the data point is transferred when a configurable trigger signal is fired. As
the trigger signal, the edge change (0 → 1) of a trigger bit is evaluated that is set by the
user program. When necessary, a separate trigger bit can be configured for each data
point.
Resetting the trigger tag in the bit memory area / DB:
If the memory area of the trigger tag is in the bit memory or in a data block, the trigger tag
is reset to zero when the data point value is transferred.
Transmission time of the frame (Transmission mode)
Whether the value of a data point is transferred to the communications partner immediately
after the trigger fires or after a delay depends on the setting of the parameter "Transmission
mode" in the "Trigger" tab of the data point:
Spontaneous
The value is transferred immediately.
Conditional spontaneous
The value is transferred only when one of the two following conditions is fulfilled:
The telecontrol server queries the station.
The value of another event with the transmission mode "Unsolicited" is transferred.
4.10.8
"Trigger“ tab
Trigger
Data points are configured as a static value or as an event using the "Type of transmission"
parameter:
Saving the value of a data point configured as an event
Saving the value of a data point configured as an event in the send buffer (message
memory) can be triggered by various trigger types:
Threshold value trigger
The value of the data point is saved when this reaches a certain threshold. The threshold
is calculated as the difference compared with the last stored value, refer to the section
Threshold value trigger (Page 101).
Time trigger
The value of the data point is saved at configurable intervals or at a specific time of day.
Event trigger (Trigger tag)
The value of the data point is saved when a configurable trigger signal is fired. For the
trigger signal, the edge change (0 → 1) of a trigger tag is evaluated that is set by the user
program. When necessary, a separate trigger tag can be configured for each data point.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CP 1243-1 and is the answer not in the manual?

Siemens CP 1243-1 Specifications

General IconGeneral
BrandSiemens
ModelCP 1243-1
CategoryConference System
LanguageEnglish

Related product manuals