Configuration
4.10 Data points
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
111
Default:
0
Explanation:
Monitors the number of pulses sent by the master station (Count). If the
number of pulses received from the master station exceeds the value co
n-
f
igured here, the command is rejected.
If you enter 0 (zero), the monitoring is disabled.
Name:
Max. pulse duration
Range of va
l-
ues:
0 ... 65535
Default:
0
Explanation:
Monitors the pulse duration sent by the master (On
-time). If the duration of
the pulse received from the master exceeds th
e value configured here, the
configurable "Pulse duration replacement time" is used.
If the "Pulse duration replacement time" is configured with zero, the co
m-
mand is rejected.
With 0 (zero) the "Pulse duration replacement time" is used for every pulse.
Name:
Pulse duration equivalent time
Range of va
l-
ues:
0 ... 65535
Default:
0
Explanation:
Replacement value for the pulse duration If the pulse duration received from
the master exceeds the value configured in “Max pulse duration“. The p
a-
r
ameter is only used when “Max. pulse duration“ is configured.
If the value is 0 (zero), no replacement value is used.
If the ""Max. pulse duration" and "Pulse duration replacement time" are co
n-
figured with zero, the command is rejected.