Configuration
4.10 Data points
CP 1243-1
90 Operating Instructions, 04/2017, C79000-G8976-C365-03
● Int, UInt, Word (total of up to 32 per data block)
● DInt, UDInt, DWord (total of up to 16 per data block)
If the array is modified later, the data point must be recreated.
Time stamps are output by the OPC server applications in UTC format (48 bits) and contain
milliseconds.
Data point types of the "DNP3" protocol
Table 4- 2 Supported data point types, DNP3 object groups, variants and compatible S7 data types
Format (memory require-
ments)
Data point type CP
[Data point type TIM]
DNP3 object
group
[variations]
Binary Input Event
[1, 2] in Bool I, Q, M, DB
1)
Binary Output Event
1)
[1, 2] out Bool Q, M, DB
2)
Frozen Counter
3)
[2, 6] in UInt, Word I, Q, M, DB
Analog Output Sta-
4)
[2] out Int Q, M, DB
Analog Output
4)
[2, 4] out Int Q, M, DB
2)
Frozen Counter
3)
[1, 5] in DWord I, Q, M, DB
Analog Input
[1] in DInt Q, M, DB
Analog Output Sta-
4)
[1, 3] out DInt Q, M, DB
Analog Output
4)
[1] out DInt Q, M, DB