CP 5623/CP 5624
Operating Instructions, 09/2013, C79000-G8976-C281-03
9
Description of the device
1
1.1
Properties of the CP 5623
Properties
The CP 5623 is a communications processor for connecting PCs (personal computers) or
PGs (programming devices) to PROFIBUS and MPI networks. The essential properties are
as follows:
Transmission speeds up to 12 Mbps.
Floating RS-485 connector.
Linking of up to 32 devices (PC, PG, SIMATIC S7 or ET 200) to form a network segment.
By linking several segments with repeaters, up to 124 nodes can be connected.
The additional interface signals for a direct link to a PLC (Programmable Logic Controller)
are supported up to 187.5 Kbps.
Installation in PGs and PCs with a PCI Express slot. The following is supported:
PCI Express x1
Can also be operated in x4, x8 and x16 slots
Plug and play
Optimized for fast DP master operation (DP Base) with up to 124 DP slaves with full data
consistency.
Relief of the PC/PG with event mechanisms.
Automatic detection of data changes.
Fast logic support regardless of the user program.
Automatic linking of input and output data can be set by the user program.
Measurement of own operating temperature with temperature sensor.
Display of the total operating hours with operating hours counter.