Commissioning
4.3 Commissioning
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB
45
Table 4- 10 Changing the function of a digital input
1. Select the required function marked using a "BI" parameter.
2. Set this parameter to the value of the status parameter r0722.x of the
required digital input.
Function
: Switch on motor via DI 2.
Setting
: p0840 = 722.2
Function
: Acknowledge fault using DI 1.
Setting
: p3981 = 722.1
Table 4- 11 Digital outputs (relay outputs)
r52.2 - operation enabled (motor running)
r52.3 - fault active
r52.7 - alarm active
Table 4- 12 Changing the function of a digital output
1. Select the required function marked using a "BO" parameter.
2. Set the parameter p073x of the required digital output to the value of the
"BO" parameter.
Function
: Signal "Fault" on DO 1.
Setting
: p0731 = 52.3
Table 4- 13 Analog inputs and temperature sensors
p0756 [0] 3 / 4 3 / 4 3 / 4 AI 0 0: Unipolar voltage input (0 V …+10 V)
1: Unipolar voltage input monitored (+2 V... +10 V)
2: Unipolar current input (0 mA …+20 mA)
3: Unipolar current input monitored (+4 mA …+20 mA)
4: Bipolar voltage input (-10 V …+10 V)
6: Ni1000 temperature sensor (-50°C … +150°C)
7: PT1000 temperature sensor (-50 …+250°C)
p0756 [3] - - 52 / 53 AI 3
Analog inputs, actual value in percent