The terminal blocks are removable for easy wiring. 
 
 
Communication 
RS232/RS485:    RX (Green) :  TX (Yellow) 
KNX:      RX (Green)   TX (Yellow)  Service (Red) 
 
The other LEDs have the following meaning: 
 
 
 
Service pin 
RUN 
Green  Continuously ON 
Power OK 
FAULT 
Red  Continuously OFF 
Continuously ON 
OK 
Fault 
Firmware missing / corrupt 
LOW 
Red  Continuously OFF 
Battery OK 
Battery emptyā replace! 
COMM 
Red  Continuously ON 
Continuously OFF 
Connection to switch OK 
No connection to switch 
SERVICE 
(Ethernet, 
PXC001-
E.D) 
Red  Continuously OFF 
Continuously ON 
Flashing 
Flashing per wink 
command *) 
OK 
No connection to switch 
No IP address configured 
Physical identification of system 
controller after receipt of wink 
SERVICE 
(LonTalk, 
PXC001.D)
Red  Continuously OFF 
Continuously ON 
 
Flashing 
Flashing per wink 
command *) 
L
ONWORKS node is configured  
Faulty L
ONWORKS chip, or service pin 
currently depressed 
L
ONWORKS node is not configured 
Physical identification of system 
controller after receipt of wink 
 
*) 
Wink command pattern: 
2s
1s
21s
5 Hz 5 Hz
9222z02
2s
1s
 
Identification of the system controller in the IP network or L
ONWORKS network  
See "Commissioning". 
 
 
Engineering 
See the PX open documents in folder CM110761. 
 
 
 