Technical data 
  Safety extra-low voltage SELV or 
  Extra-low voltage PELV 
External fusing (compulsory) 
External fuse protection for secondary 
current: Slow blow fusible link Max. 10
 A,
 
circuit breaker Max. 13 A type C, or
 
transformer with secondary current 
limitation of max. 10 A  
64MB SDRAM / 32MB FLASH  
(96MB total) 
Data backup in event of power failure 
Battery Backup of realtime clock  
Lithium CR2032 (field replaceable)  
Battery operation (cumulative): 1 month 
Without load: 10 years  
Battery backup for SDRAM  
1 x FR6/AA Lithium (field replaceable) 
Battery operation (cumulative): 1 month 
Without load: 10 years 
Interfaces, communication 
PXC001.D  PXC001-E.D 
LonWorks FT5000 Transceiver  
Twisted Pair, 78 kBit/s 
(Screw terminals) 
IEEE802.3, Auto-sensing  
10 Base-T / 100 Base-TX 
(HMI, Tool) 
•  PXM20 (BACnet/LonTalk, RJ45)  
•
Local Communication  
 (HMI) 
•  PXM10 (RS232)  
•  PXM20 (BACnet/LonTalk) (RJ45) 
One PXM10 operator unit and one 
PXM20 per system controller may be 
connected. But not twice the same 
KNX (electrically isolated) 
Bus topology, bus termination 
300, 600, 1200, 2400, 4800, 9600, 
19200, 38400 
7 or 8 (depending on software) 
1 or 2 (depending on software) 
None, even or odd 
(depending on software) 
Xon/Xoff, hardware or none 
(depending on software) 
9-core standard screened cable 
Max. 3 m 
7 / 10 
Siemens  PXC001   System controllers  CM1N9223en_01 
Building Technologies    2014-04-04