Use 
•  The system controllers support the integration of Desigo RXB/RXL room 
controllers as well as third-party devices and systems via KNX, Modbus or M-
Bus etc. in the automation level using BACnet/LonTalk or BACnet/IP 
•  Mapping and monitoring of third-party disciplines as HVAC, light, SPS etc. 
•  Functionality as freely programmable system controllers for standard or 
proprietary protocol applications 
Functions  
•  The system controllers provide the infrastructure to hold and execute the system 
and application specific functions. They are freely programmable. 
•  Comprehensive management and system functions are available: 
−  Alarm management 
−  Time scheduling 
−  Trends 
−  Access protection 
Type summary 
 
System-Controller for the integration of KNX, M-Bus, Modbus 
or SCL over BACnet/LonTalk  
System-Controller for the integration of KNX, M-Bus, Modbus 
SCL: up to 1000 data points,  
M- Bus and Modbus: up to 2000 data points) 
PXA40-RS2 
 
Equipment combinations 
 
 
PXA40-… option modules can be plugged and unplugged when the automation 
station is operating. 
•  The functionality is available immediately after inserting. 
•  The functionality disappears approx.1 minute after unplugging. 
 
Option modules are 
"hot-pluggable" 
2 / 10 
Siemens  PXC001   System controllers  CM1N9223en_01 
Building Technologies    2014-04-04