6...7.5 mm (0.24...0.29 in)
Slot screws, screwdriver size 1
The two COM interfaces can be used either for Modbus or for MS/TP, according to
configuration.
EIA-485, electrically isolated
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(depending on the configuration)
120 Ohm, switchable with DIP switch
Internal bus polarization
270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only)
Cable length
3-wire cable
Max. 1000 m (3300 ft)
Short-circuit proof
Protection against faulty wiring with AC 24 V
EIA-485, electrically isolated
9600, 19200, 38400, 57600, 76800, 115200 (depending
on the configuration)
120 Ohm, switchable with DIP switch
Internal bus polarization
270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only)
Distance between 2 devices
Length of the MS/TP line
3-wire cable, shielded
Max. 500 m (1650 ft)
Max. 1000 m (3300 ft)
Short-circuit proof
Protection against faulty wiring with AC 24 V
Supported standards
Frequency band
WLAN channels
Maximum radio-frequency power
IEEE 802.11b/g/n
2.4…2.462 GHz
1…11
16.4 dBm
Distance (unobstructed field)
Activation / Deactivation with service button
Automatic switch off after 10 minutes if no WLAN-client
is connected.
Optionally, for cyber security reasons, the WLAN can be
permanently disabled via configuration.
Default SSID and WLAN password: Scan the QR code.
It will show something like WIFI:S:PXC5.E003_0000550;T:WPA;P:1400052738;;
Then SSID = PXC5.E003_0000550 and password = 1400052738
Determine manually: Use the information from the Date/Series/SN block It will show something like:
Date/Series: 20190423A0000550
S/N: 1400052738
SSID = <ASN>_<Running number after the series letter> and password = <S/N>