Siemens…………………….RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S Basic Documentation CE1P3171en
Smart Infrastructure 2020-02-21
On 4-pipe applications, the Comfort setpoint (w) is in the middle of the dead zone,
between the heating and cooling sequence.
The dead zone can be adjusted via parameter P33.
If manual changeover is selected, then either the cooling sequence or the heating
sequence is released. In this case, the Comfort setpoint is at the selected heating
or cooling sequence.
Comfort mode
Economy /
Protection mode
Application Heating and cooling Heating only
1)
Cooling only
1)
Heating and/or
cooling
4-pipe
1) Manual changeover, P01 = 2
W = setpoint in Comfort mode
W
HeatEco/Prot
= heating setpoint for Economy or Protection mode
W
CoolEco/Prot
= cooling setpoint for Economy or Protection mode
YE = electric heater sequence
4
-
pipe applications
Y
T
W
H
eatE
co
/P
rot
W
CoolE
co
/P
rot
Y
T
W
Y
T
W
Y
T
W