Standard I/O Modules
58 Unrestricted SICAM A8000 Series, SICAM I/O Modules
DC8-012-2.06, Edition 09.2019
2.8.5 Block Diagram
Note
For the measurement of currents,
the current transformer module CM-8820 is to be connected ahead of
AI
-8510. The specification for the connection cable can be found in section 2.10.3, Technical Data.
Danger
The connectors X1 and X2 may be detached or attached in de
-energized state only!
The connector X1 must always be plugged during operation (even if no current measurement is used)!
Warning
The
inputs of connector X1 must not be connected directly with a mains supply circuit!
The inputs
of connector X2 may be connected directly with system current circuits up to AC 240/415 V.
H
igher voltages must be adapted via interconnected voltage transformers!
Note
T
ake account of the direction of current flow when connecting the current measuring inputs. With inverse
connection, the measured values are inverted and receive a negative sign.
The same applies
correspondingly for the voltage measurement (direction and phase angle).
FE
X2
1
2
3
4
5
6
7
8
9
X1
1
2
3
4
5
6
7
8
9
10
DNC
N
N
N
DNC
DNC
I3-
DNC
DNC
I1+
I1-
I3+
A
D
U3
U2
U1
I2-/IN-
I2-
/IN
+
FE Shield
CC Shield
PIC Processor 18F45K22
reinforced insulation
internal BUS
AI-8510