Standard I/O Modules
SICAM A8000 Series, SICAM I/O Modules Unrestricted 61
DC8-012-2.06, Edition 09.2019
2.8.6.3.1 3-Phase Voltage, 3-Phase Current
Through the current inputs I1, I2/IN, I3 the corresponding phase currents are measured. The
value IN is calculated.
This configuration is used for solidly grounded networks. In this configuration, the module
works also as a power meter.
Example: Middle-voltage network
1
2
3
4
5
6
7
8
9
10
X1
AI-8510
225 mV
225 mV
225 mV
P2P1
P2
P1
P2
P1
S2S1
S2
S1
S2
S1
1 A
1 A
1 A
1
2
3
4
5
6
X1
1
2
3
4
5
6
7
8
9
10
I1_P
I1_N
I2_P
I2_N
I3_P
I3_N
DNC
I3-
DNC
DNC
I1+
I1-
I3+
CM-8820
X2
FE Shield
I2-/IN-
I2-/IN+
1
2
3
4
5
6
7
8
9
10
X1
CM-8820
225 mV
225 mV
225 mV
BABA
B
A
baba
b
a
2
0 kV
20 kV
20 kV
100 V/√3
100 V/√3
100 V/√3
N
L3
L2
L1
AI-8510
X2
1
2
3
4
5
6
7
8
9
X1
1
2
3
4
5
6
7
8
9
10
DNC
N
N
N
DNC
DNC
I3-
DNC
DNC
I1+
I1-
I3+
I2-/IN-
I2-/IN+
U3
U2
U1
FE Shield
CC Shield