EasyManuals Logo

Siemens FC901-R3 User Manual

Siemens FC901-R3
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
Scenario 2 – Must/Can
Alarm Event is set to Must Report on Account 1 and Can
Report on Account 2. Panel fails on Account 1 the first
time.
Step 1:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
N
Account 1
Account 2
Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.
Step 4:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N
Account 1
Account 2
Step 5:
Panel keeps trying to send event to Account 2 until the programmed Number
Of Attempts has been reached.
Done.
68

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC901-R3 and is the answer not in the manual?

Siemens FC901-R3 Specifications

General IconGeneral
BrandSiemens
ModelFC901-R3
CategoryControl Panel
LanguageEnglish

Related product manuals