Fig. 23: Hole after fitting
5.2.6 Connecting the pipe system to the aspirating smoke
detector
w The pipe system has been mounted.
w The first 500mm of a pipe system with an aspirating smoke detector are
configured in a straight line so any flow turbulence can settle before the air
enters the aspirating smoke detector.
1. NOTICE!It must be possible to detach the connection to the aspirating
smoke detector in order to perform maintenance – this connection must
not be glued.
Press the short pipe into the air inlet of the aspirating smoke detector.
2. Connect the pipe system to the pressed-in pipe.
a The pipe system is connected to the aspirating smoke detector.
Mounting/Installation
Mounting the pipe system
5
A6V11783979_en--_a 45 | 48