3
Mounting
Adapting the front indicator to the installation position
3 Mounting
3.1 Adapting the front indicator to the installation
position
The aspirating smoke detector can be installed rotated by 180° if required. The
front indicator must then also be installed rotated by 180°.
180°
8x
8x
1
2
4
3
Adapting the front indicator to the installation position
The housing cover has been removed (step 1).
1. Loosen the 8 screws on the inside of the housing cover (step 2).
2. Rotate the front indicator by 180° (step 3).
3. Fasten the front indicator to the housing cover using the 8 screws (step 4).
The front indicator is adapted to the installation position.
16
Building Technologies A6V10345654_h_en_--
Fire Safety 2015-05-29
firealarmresources.com