EasyManua.ls Logo

Siemens FibroLaser III - Cleaning Fibre-Optical Connectors

Siemens FibroLaser III
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
15
Building Technologies FL-III Maintenance and Repair
CPS Fire Safety 08.2012
Recommendations:
Cleaning cloth Lint-free and suitable for the cleaning of optical components
in accordance with the specifications, such as:
- KIMTECH Science KIMWIPE® EX-L
- Chemtronics OpticWipes
TM
- Newport Optics Cleaning Tissue
Solvents Ethanol or isopropanol in accordance with the specifications
for the use in UV spectroscopy or in a similar ultra-pure
quality (>99.9%), such as:
- Merck Uvasol®
- Sigma-Aldrich spectrophotometric grade
Ferrule cleaner
- SEIKOH GIKEN Ferrule Mate
TM
End-face cleaner
SFM250 E2000
CAUTION!
Use only microscopes for fibre-optical connectors with a laser safety filter
(1550 nm, DIR LB3) in accordance with the requirements as specified in EN 207.
Please refer to the manufacturer’s documentation provided with the equipment
for detailed instructions on the operation of the microscope.
3.3.2 Cleaning the fibre-optical connectors
Fig. 7 Fibre-optical connector (E2000/APC) of the sensor cable