Fault Diagnostics
26
Building Technologies FL-III Maintenance and Repair
CPS Fire Safety 08.2012
4.2.3 Warnings
Name
System
address point
Description Troubleshooting
Configuration
warning
201 Configuration data is not valid. Repeat the commissioning
procedure. Send the support
information to the technical support
department, if required.
Measurement
warning
202 Single invalid measurement. This
measurement is ignored, and
measurements are continued.
Check the environmental conditions
as well as the sensor cable and / or
repeat the commissioning if this
warning occurs repeatedly. Send
the support information to the
technical support department, if
required.
Environmental
conditions
warning
203 Supply voltage, temperature and /
or moisture are close to the
permissible limit values.
Provide environmental conditions in
accordance with the specifications.
Improve the air circulation around
the controller.
Communication
warning
204 Low quality of data transmission. Check type and lengths of the
communication cables as well as
network settings.
Tab. 7 Warnings / recommendations for troubleshooting
4.2.4 Messages
Name
System
address point
Description
Acknowledgement 51 Acknowledgement has been triggered by key switch, FibroManager,
communication protocol or input.
Reset 52 Reset has been triggered by key switch, Fibromanager,
communication protocol or input.
Test mode
activated
53 Test mode has been activated or deactivated. Simulation of inputs,
outputs, fibre breaks and / or alarms.
Test mode
deactivated
54 Test mode has been deactivated.
Firmware
upload
- A new firmware version has been uploaded to the controller.
System start - System has been started.
Output - Output state has been changed.
Inputs
1 to 40
1 to 40 Alarm, reset or acknowledgement input has been activated. Control
input has been activated or deactivated.
Tab. 8 Information messages